Select Date Home
Transmission Elements Outage Report for 10-09-2016

A. Details of Transmission Elements under Planned Outage:-
S.No Element Name Type Voltage Level Owner Outage Revival Expected Date of Revival Reason / Remarks
Date Time Date Time
1 Fatehpur 1500 MVA ICT 1 ICT 765/400 kV PGCIL 10-09-2016 15:58 10-09-2016 18:36 - For CSD Commissioning .
2 765 kV Bhiwani-2 / ICT-2 Tie Bay(702-52T) at Phagi BAY/CB 765 kV RRVPNL 23-08-2016 11:07 * * 11-09-2016 For erection and commissioning of Bhiwani-II main bay equipments at Phagi
3 765 kV / 400kV ICT-1 Main Bay (703) at Fatehpur PG BAY/CB 765 kV PGCIL 10-09-2016 10:54 10-09-2016 12:45 - For CSD Commissioning works.
4 765 kV Gaya-1/ ICT-1 Tie Bay (702) at Fatehpur PG BAY/CB 765 kV PGCIL 10-09-2016 13:06 10-09-2016 18:36 - For CSD Commissioning works.
5 Ballabgarh-Kanpur 1 Line 400 kV PGCIL 10-09-2016 09:15 10-09-2016 19:46 - For replacement of Tie Bay isolator( Ballabhagarh -1 Line side-41689A) at Kanpur PG under Add Cap
6 400kV G.Noida(UP)-Nawada(HVPNL) Line 400 kV PGCIL 10-09-2016 09:56 10-09-2016 15:44 - To replace the 400kV Isolator blades at Nawada and maintenance of isolator of Bus-1 at Nawada by HVPNL.
7 Daultabad(HVPNL)-Gurgaon(PG) -1 Line 400 kV HVPNL 10-09-2016 10:40 10-09-2016 19:02 - For GIS Bay-408 AMP Works at Gurgaon end by Powergrid NR-1.
8 Kankroli-Zerda Line 400 kV PGCIL 10-09-2016 15:05 10-09-2016 15:38 - To take line reactor Out of service at Kankroli end.
9 Kankroli-Zerda Line 400 kV PGCIL 10-09-2016 19:11 10-09-2016 19:28 - To take line reactor In serviceat Kankroli end.
10 Ballabgarh 315 MVA ICT 2 ICT 400/220 kV PGCIL 08-08-2016 10:26 * * 11-09-2016 For retrofittment ( replacement for capacity addition) of this 315 MVA ICT 2 with new 500MVA ICT 2 at Ballabhagarh PG.
11 New Wanpoh 125 MVAR B/Reactor 1 Bus Reactor 400 kV PGCIL 27-04-2015 18:29 * * NA Take out due to low voltage.
12 Kisanpur 80 MVAR B/R Bus Reactor 400 kV PGCIL 02-02-2016 08:05 * * NA For voltage regulation.
13 Nawada 400 kV Bus 1 BUS 400 kV HVPNL 10-09-2016 10:09 10-09-2016 15:44 - To replace the 400kV Isolator blades of Gr.Noida-Nawada line bay at Nawada and maintenance of isolator of Bus-1 at Nawada by HVPNL.
14 Kanpur(PG)-Unchahar(NTPC) 1 Line 220 kV PGCIL 01-09-2016 12:01 10-09-2016 13:29 - For complete replacement of protection panes by numerical relays module at Unchahar end by NTPC.
15 Mainpuri(PG)-Mainpuri(UP) 1 Line 220 kV UPPTCL 09-09-2016 16:38 * * NA Replacement of CVT.
16 FSC of Pampore-1 at Kishnpr FSC 220 kV PGCIL 30-10-2012 12:00 * * NA LILO work of line .
17 FSC of Pampore-2 at Kishnpr FSC 220 kV PGCIL 30-10-2012 12:00 * * NA LILO work of line .
*-Line still under outage     NA - Not Available

B. Details of Transmission Elements under Forced Outage:-
S.No Element Name Type Voltage Level Owner Outage Revival Expected Date of Revival Reason / Remarks
Date Time Date Time
1 Gwalior (PG) - Phagi (RVPNL) - 1 Line 765 kV PGCIL 10-09-2016 13:24 10-09-2016 14:29 - PLCC maloperation.
2 Gwalior (PG) - Phagi (RVPNL) - 1 Line 765 kV PGCIL 10-09-2016 15:00 10-09-2016 16:18 - PLCC maloperation.
3 Anta RS 1500 MVA ICT 1 ICT 765/400 kV RRVPNL 17-08-2016 09:04 * * NA Manually opened due to fire in control panel
4 G.Noida 765 (3*80) 240 MVAR (765kV) Bus Reactor 1 Bus Reactor 765 kV UPPTCL 06-08-2016 10:32 * * NA To attend hot spot To attend Buchholz alarm in R phase
5 Bamnauli(DTL)-Jatikala(PG) 1 Line 400 kV DTL 22-05-2016 20:29 * * NA Tower damage (First dead end tower from Bamnauli S/S) / Ckt-II charge through ERS tower
6 Anta RS - Chabra -1 Line 400 kV RRVPNL 19-08-2016 20:45 * * NA keep open on overvoltage.
7 Alaknanda HEP - Muzaffarnagar - 2 Line 400 kV UPPTCL 10-09-2016 10:00 10-09-2016 10:31 - B-phase to earth fault
8 400kV Ballabgarh(PG)-Nawada(HVPNL) Line 400 kV PGCIL 10-09-2016 15:54 10-09-2016 20:54 - For replacement of 400kV Isolators Blades (Y & B phase ) of 400kV Bus-I at Nawda end.
9 Anpara-Sarnath 2 Line 400 kV UPPTCL 10-09-2016 19:48 10-09-2016 21:02 - Tripped details awaited.
10 Agra-Muradnagar Line 400 kV UPPTCL 10-09-2016 21:55 10-09-2016 22:37 - Tripped on Y-Phase to earth fault
11 Kalisindh 315 MVA ICT ICT 400/220 kV RRVPNL 04-06-2016 15:50 * * NA Buchholz relay operated.
12 Jodhpur II 315 MVA ICT 2 ICT 400/220 kV RRVPNL 10-08-2016 01:40 * * NA BUCHHOLZ Relay operated.
13 Gorakhpur 315 MVA ICT ICT 400/220 kV UPPTCL 10-09-2016 04:05 10-09-2016 05:30 - Trippped due to earth fault in 220kV gkp-Deoria
14 Bareilly 50 MVAR B/R Bus Reactor 400 kV UPPTCL 05-08-2007 00:00 * * NA Failure of Reactor.
15 Sarnath 50 MVAR B/R Bus Reactor 400 kV UPPTCL 16-02-2009 06:14 * * NA Failure of Reactor.
16 FSC of Bareilly-I at Unnao FSC 400 kV PGCIL 19-04-2015 13:10 * * NA Fire in FSC.
17 Wagoora 50 MVAR B/R Bus Reactor 400 kV PGCIL 22-04-2015 18:56 * * NA Take out due to low voltage.
18 FSC ( 50% ) of Koteshwar Pool -1 at Meerut (PG) FSC 400 kV PGCIL 16-07-2015 13:01 * * NA Fire in FSC-2 at Meerut.
19 FACT at BLB in Knp-BLB Line FACTS 400 kV PGCIL 02-07-2016 10:20 * * NA Y-Phase current imbalance
20 Kankroli 400 kV Bus 1 BUS 400 kV PGCIL 10-09-2016 14:37 10-09-2016 15:16 - To attend lockout of Zerda bay CB at Kankroli end
*-Line still under outage     NA - Not Available

C. Details of Transmission Elements Opened manually due to High Voltage:-
S.No Element Name Type Voltage Level Owner Outage Revival Remarks
Date Time Date Time
1 Anta RS - Chabra -2 Line 400 kV RRVPNL 28-07-2016 17:27 ** **  
2 Ajmer II-Didwana Line 400 kV RRVPNL 09-09-2016 16:33 10-09-2016 09:41  
3 Heerapura-Merta Line 400 kV RRVPNL 09-09-2016 17:05 10-09-2016 09:52  
4 Agra-Sikar 1 Line 400 kV PGCIL 09-09-2016 17:16 10-09-2016 10:36  
5 Ratangarh (RVPNL) - Sikar (PG) - 2 Line 400 kV PGCIL 09-09-2016 17:16 10-09-2016 09:59  
6 Ratangarh (RVPNL) - Sikar (PG) - 1 Line 400 kV PGCIL 10-09-2016 16:11 ** **  
7 Bikaner-Didwana 1 Line 400 kV RRVPNL 10-09-2016 16:16 10-09-2016 19:24  
8 Ratangarh-Suratgarh 2 Line 400 kV RRVPNL 10-09-2016 16:56 ** **  
9 Ajmer II-Didwana Line 400 kV RRVPNL 10-09-2016 17:47 ** **  
10 Kota(PG)-Merta(RVPNL) 1 Line 400 kV PGCIL 10-09-2016 18:06 10-09-2016 19:24  
11 Kota(PG)-Merta(RVPNL) 1 Line 400 kV PGCIL 10-09-2016 21:25 ** **  
** - Line shall be closed subject to voltage permissibility