| S.No |
Element Name |
Type |
Voltage Level |
Owner |
Outage |
Revival |
Expected Date of Revival |
Reason / Remarks |
| Date |
Time |
Date |
Time |
| 1 |
Jatikala-Kanpur New |
Line |
765 kV |
PGCIL |
20-11-2016 |
07:47 |
20-11-2016 |
19:09 |
- |
For jumper tightening / CC VD fixing |
| 2 |
765 kV Bus Reactor -1 Main Bay (703) at Moga PG |
BAY/CB |
765 kV |
PGCIL |
19-11-2016 |
09:45 |
* |
* |
20-11-2016 |
For AMP of bays equipments. |
| 3 |
Agra-Bhiwadi 2 |
Line |
400 kV |
PGCIL |
14-11-2016 |
11:14 |
* |
* |
22-11-2016 |
Diverson of Line --- for tower erection and diversion works due to infringement in DFCC corridor ( work is being done by Powergrid) |
| 4 |
Agra-Bhiwadi 1 |
Line |
400 kV |
PGCIL |
14-11-2016 |
11:14 |
* |
* |
22-11-2016 |
Diverson of Line --- for tower erection and diversion works due to infringement in DFCC corridor ( work is being done by Powergrid) |
| 5 |
Lucknow-Unnao |
Line |
400 kV |
UPPTCL |
20-11-2016 |
08:09 |
20-11-2016 |
19:46 |
- |
For complete over hauling of 29 A and 29 C isolator of Lucknow UP line at Unnao end along with the 29 A isolator of Bus coupler at Unbao. |
| 6 |
Bhinmal-Zerda |
Line |
400 kV |
PGCIL |
20-11-2016 |
09:56 |
20-11-2016 |
16:06 |
- |
Shutdown by WRLDC. |
| 7 |
Dhuri (400kV)-Rajpura (400kV)-2 |
Line |
400 kV |
PSEB |
20-11-2016 |
10:07 |
* |
* |
21-11-2016 |
Tightening of jumpers ,dampers, suspension clamps and cleaning of disc insulator in the line between loc no.81 to 96 by PSTCL. |
| 8 |
Muzaffarnagar-Vishnuprayag 1 |
Line |
400 kV |
UPPTCL |
20-11-2016 |
11:31 |
20-11-2016 |
18:35 |
- |
Polymer insulator replacement--- for replacement of porcelain disc insulators with polymer insulators strings in the line. |
| 9 |
Dehar 250 MVA ICT |
ICT |
400/220 kV |
BBMB |
15-10-2016 |
08:02 |
* |
* |
11-12-2016 |
Construction of new element For replacement of 400/220 ,250 MVA ICT (3*83.3 MVA + one spare unit 83.3 MVA) and its associate bay equipments with 315 MVA ICT (3*105 MVA + I spare unit 105 MVA) Transformers of 400/220 KV CGL make under Northern Region Strengthening Scheme at BBMB Dehar.The replacement work will be carried out by PGCIL. |
| 10 |
Dhuri(400) 500 MVA ICT 2 |
ICT |
400/220 kV |
PSEB |
17-11-2016 |
10:26 |
* |
* |
23-11-2016 |
Emergency SD for Complete internal inspection due to Detection of high C2H2 from the test result of PD test conducted at site |
| 11 |
Nakodar 315 MVA ICT 2 |
ICT |
400/220 kV |
PSEB |
19-11-2016 |
08:43 |
20-11-2016 |
16:45 |
- |
Completion, testing and commissioning of HVWSS system |
| 12 |
TCSC of MUZPR-I at GRKP |
TCSC |
400 kV |
PGCIL |
17-09-2016 |
11:23 |
* |
* |
NA |
Block problem of Y &B phase. |
| 13 |
Jalandhar(PG) 125 MVAR (400kV) Bus Reactor 1 |
Bus Reactor |
400 kV |
PGCIL |
07-10-2016 |
11:03 |
* |
* |
30-11-2016 |
For shifting of Bus reactor in ICT-3 diafor vacating its bays for LILO of 400kV Amritsar-Parbati line at Jalandhar by Powergrid. |
| 14 |
New Wanpoh 125 MVAR B/Reactor 1 |
Bus Reactor |
400 kV |
PGCIL |
10-10-2016 |
10:09 |
* |
* |
NA |
Take out due to low voltage. |
| 15 |
FSC ( 50% ) of Koteshwar Pool -1 at Meerut (PG) |
FSC |
400 kV |
PGCIL |
04-11-2016 |
09:10 |
* |
* |
30-11-2016 |
To facilitating Bay extension works at Meerut and erection works of 02 nos of dead end tower. |
| 16 |
Sultanpur 400 kV Bus 1 |
BUS |
400 kV |
UPPTCL |
07-11-2016 |
13:15 |
* |
* |
30-11-2016 |
For erection and commissioning of new Bus bar protection panel in place of old Bus Bar protection panel. |
| 17 |
Bikaner 400 kV Bus 1 |
BUS |
400 kV |
RRVPNL |
15-11-2016 |
11:50 |
20-11-2016 |
16:19 |
- |
Jumpering and maintenance works. |
| 18 |
Koteshwar Pool 400 kV Bus 1 |
BUS |
400 kV |
PGCIL |
19-11-2016 |
09:57 |
* |
* |
21-11-2016 |
Replacement of isolator contacts of Tehri-2 line at Koteshwar(PG)-GIS With Bus-1. |
| 19 |
Unnao 400 kV Bus 1 |
BUS |
400 kV |
UPPTCL |
20-11-2016 |
08:09 |
20-11-2016 |
19:46 |
- |
For complete over hauling of 29 A and 29 C isolator of Lucknow UP line at Unnao end along with the 29 A isolator of Bus coupler at Unbao. |
| 20 |
Patiala(PG)-Rajpura(PSEB) |
Line |
220 kV |
PSEB |
11-11-2016 |
13:05 |
* |
* |
26-11-2016 |
To augment present single 220kv Busbar with double 220kv Busbar at Rajpura PSTCL. |
| 21 |
AD Hydro(ADHY)-Nallagarh(PG) 1 |
Line |
220 kV |
ADHYDRO |
20-11-2016 |
10:34 |
20-11-2016 |
17:42 |
- |
1.For Pre-winter maintenance works ( tightening of jumpers, tower parts,VD & cleaning of insulators etc , and lopping /chopping of trees and rectification of loose sags if any. |
| 22 |
FSC of Pampore-2 at Kishnpr |
FSC |
220 kV |
PGCIL |
30-10-2012 |
12:00 |
* |
* |
NA |
Line length has reduced after LILO work completion |
| 23 |
FSC of Pampore-1 at Kishnpr |
FSC |
220 kV |
PGCIL |
30-10-2012 |
12:00 |
* |
* |
NA |
Line length has reduced after LILO work completion |