Back

Voltage Analysis For 400 KV Singrauli Substation For :   15-04-2005

A. Voltage Trend:







































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































(Note: The figures shown above are indicative only and are calculated based on data acquired from remote locations
in Northern Region over existing communication links.)

B. Voltage Duration Curve:


(Note: The figures shown above are indicative only and are calculated based on data acquired from remote locations
in Northern Region over existing communication links.)

C. Summary Report:

Voltage Greater Than Percentage of Time
440 0
430 0
420 0
412 64.6
388 100
380 100
370 100
360 100
Maximum KV 417 KV at 18:30 Hrs.
Minimum KV 409 KV at 04:34 Hrs.
Average KV 412 KV
% of Time Voltage (All values in %)
Between 388-412 KV 35.40
Between 360-420 KV 100.00
<360 KV 00.00
<370 KV 00.00
<380 KV 00.00
<388 KV 00.00
>412 KV 64.60
>420 KV 00.00
>430 KV 00.00
>440 KV 00.00

D. Hourly Values:

Hour KV Hour KV
01:00 412 13:00 400
02:00 413 14:00 400
03:00 412 15:00 400
04:00 411 16:00 412
05:00 411 17:00 414
06:00 410 18:00 414
07:00 410 19:00 413
08:00 412 20:00 412
09:00 413 21:00 412
10:00 413 22:00 412
11:00 411 23:00 413
12:00 411 24:00 414