Back

Voltage Analysis For 400 KV Jullandhar PG Substation For :   11-12-2004

A. Voltage Trend:


































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































(Note: The figures shown above are indicative only and are calculated based on data acquired from remote locations
in Northern Region over existing communication links.)

B. Voltage Duration Curve:


(Note: The figures shown above are indicative only and are calculated based on data acquired from remote locations
in Northern Region over existing communication links.)

C. Summary Report:

Voltage Greater Than Percentage of Time
440 0
430 0
420 18.06
412 61.33
388 100
380 100
370 100
360 100
Maximum KV 428 KV at 17:17 Hrs.
Minimum KV 400 KV at 11:03 Hrs.
Average KV 413 KV
% of Time Voltage (All values in %)
Between 388-412 KV 38.67
Between 360-420 KV 81.94
<360 KV 00.00
<370 KV 00.00
<380 KV 00.00
<388 KV 00.00
>412 KV 61.33
>420 KV 18.06
>430 KV 00.00
>440 KV 00.00

D. Hourly Values:

Hour KV Hour KV
01:00 418 13:00 418
02:00 423 14:00 404
03:00 421 15:00 411
04:00 415 16:00 408
05:00 416 17:00 420
06:00 410 18:00 403
07:00 412 19:00 407
08:00 419 20:00 413
09:00 416 21:00 424
10:00 411 22:00 418
11:00 409 23:00 420
12:00 402 24:00 417