Voltage Analysis For 400 KV Kishenpur Substation For : 11-12-2004
A. Voltage Trend:
(Note: The figures shown above are indicative only and are calculated based on data acquired from remote locations
in Northern Region over existing communication links.)
B. Voltage Duration Curve:
(Note: The figures shown above are indicative only and are calculated based on data acquired from remote locations
in Northern Region over existing communication links.)
C. Summary Report:
| Voltage Greater Than | Percentage of Time |
| 440 | 0 |
| 430 | 0 |
| 420 | 0.31 |
| 412 | 4.73 |
| 388 | 99.76 |
| 380 | 100 |
| 370 | 100 |
| 360 | 100 |
| Maximum KV | 424 KV at 17:17 Hrs. |
| Minimum KV | 387 KV at 17:57 Hrs. |
| Average KV | 402 KV |
| % of Time Voltage | (All values in %) |
| Between 388-412 KV | 95.03 |
| Between 360-420 KV | 99.69 |
| <360 KV | 00.00 |
| <370 KV | 00.00 |
| <380 KV | 00.00 |
| <388 KV | 00.24 |
| >412 KV | 04.73 |
| >420 KV | 00.31 |
| >430 KV | 00.00 |
| >440 KV | 00.00 |
D. Hourly Values:
| Hour | KV | Hour | KV |
| 01:00 | 407 | 13:00 | 410 |
| 02:00 | 411 | 14:00 | 394 |
| 03:00 | 409 | 15:00 | 401 |
| 04:00 | 402 | 16:00 | 397 |
| 05:00 | 404 | 17:00 | 410 |
| 06:00 | 397 | 18:00 | 390 |
| 07:00 | 398 | 19:00 | 395 |
| 08:00 | 408 | 20:00 | 402 |
| 09:00 | 408 | 21:00 | 414 |
| 10:00 | 402 | 22:00 | 405 |
| 11:00 | 402 | 23:00 | 406 |
| 12:00 | 395 | 24:00 | 405 |