Voltage Analysis For 400 KV Wagoora Substation For :   13-12-2004

A. Voltage Trend:


































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































(Note: The figures shown above are indicative only and are calculated based on data acquired from remote locations
in Northern Region over existing communication links.)

B. Voltage Duration Curve:


(Note: The figures shown above are indicative only and are calculated based on data acquired from remote locations
in Northern Region over existing communication links.)

C. Summary Report:

Voltage Greater Than Percentage of Time
440 0
430 0
420 0
412 0
388 0
380 11.48
370 52.94
360 86.66
Maximum KV 387 KV at 01:06 Hrs.
Minimum KV 350 KV at 07:17 Hrs.
Average KV 370 KV
% of Time Voltage (All values in %)
Between 388-412 KV 00.00
Between 360-420 KV 11.48
<360 KV 13.34
<370 KV 47.06
<380 KV 88.52
<388 KV 100.00
>412 KV 00.00
>420 KV 00.00
>430 KV 00.00
>440 KV 00.00

D. Hourly Values:

Hour KV Hour KV
01:00 383 13:00 381
02:00 380 14:00 363
03:00 377 15:00 369
04:00 373 16:00 365
05:00 376 17:00 369
06:00 372 18:00 364
07:00 355 19:00 359
08:00 374 20:00 364
09:00 379 21:00 354
10:00 373 22:00 371
11:00 371 23:00 376
12:00 369 24:00 382