Back

Voltage Analysis For 400 KV Muradnagar Substation For :   15-04-2005

A. Voltage Trend:







































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































(Note: The figures shown above are indicative only and are calculated based on data acquired from remote locations
in Northern Region over existing communication links.)

B. Voltage Duration Curve:


(Note: The figures shown above are indicative only and are calculated based on data acquired from remote locations
in Northern Region over existing communication links.)

C. Summary Report:

Voltage Greater Than Percentage of Time
440 0
430 0
420 0
412 0
388 90.33
380 100
370 100
360 100
Maximum KV 404 KV at 01:57 Hrs.
Minimum KV 383 KV at 06:13 Hrs.
Average KV 394 KV
% of Time Voltage (All values in %)
Between 388-412 KV 90.33
Between 360-420 KV 100.00
<360 KV 00.00
<370 KV 00.00
<380 KV 00.00
<388 KV 09.67
>412 KV 00.00
>420 KV 00.00
>430 KV 00.00
>440 KV 00.00

D. Hourly Values:

Hour KV Hour KV
01:00 400 13:00 400
02:00 403 14:00 400
03:00 400 15:00 400
04:00 394 16:00 393
05:00 394 17:00 397
06:00 388 18:00 395
07:00 391 19:00 395
08:00 401 20:00 392
09:00 395 21:00 394
10:00 393 22:00 398
11:00 388 23:00 395
12:00 390 24:00 402