Back

Voltage Analysis For 400 KV Muradnagar Substation For :   19-11-2004

A. Voltage Trend:


































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































































(Note: The figures shown above are indicative only and are calculated based on data acquired from remote locations
in Northern Region over existing communication links.)

B. Voltage Duration Curve:


(Note: The figures shown above are indicative only and are calculated based on data acquired from remote locations
in Northern Region over existing communication links.)

C. Summary Report:

Voltage Greater Than Percentage of Time
440 0
430 0
420 0
412 0
388 76.98
380 99.27
370 100
360 100
Maximum KV 410 KV at 23:44 Hrs.
Minimum KV 376 KV at 10:05 Hrs.
Average KV 395 KV
% of Time Voltage (All values in %)
Between 388-412 KV 76.98
Between 360-420 KV 99.27
<360 KV 00.00
<370 KV 00.00
<380 KV 00.73
<388 KV 23.02
>412 KV 00.00
>420 KV 00.00
>430 KV 00.00
>440 KV 00.00

D. Hourly Values:

Hour KV Hour KV
01:00 407 13:00 387
02:00 404 14:00 383
03:00 405 15:00 391
04:00 403 16:00 391
05:00 402 17:00 393
06:00 398 18:00 394
07:00 395 19:00 393
08:00 401 20:00 400
09:00 391 21:00 401
10:00 381 22:00 403
11:00 387 23:00 403
12:00 385 24:00 405