Back

Voltage Analysis For 220 KV IP Substation For :   19-11-2004

A. Voltage Trend:























B. Voltage Duration Curve:


(Note: The figures shown above are indicative only and are calculated based on data acquired from remote locations
in Northern Region over existing communication links.)

C. Summary Report:

Voltage Greater Than Percentage of Time
245 0
240 0
230 0
227 0.07
213 82.81
210 99.16
200 99.99
190 99.99
Maximum KV 227 KV at 23:44 Hrs.
Minimum KV 208 KV at 10:05 Hrs.
Average KV 217 KV
% of Time Voltage (All values in %)
Between 213-227 KV 82.74
Between 200-245 KV 99.90
<190 KV 00.00
<200 KV 00.00
<210 KV 00.83
<213 KV 17.18
>227 KV 00.07
>230 KV 00.00
>240 KV 00.00
>245 KV 00.00

D. Hourly Values:

Hour KV Hour KV
01:00 224 13:00 214
02:00 222 14:00 213
03:00 223 15:00 216
04:00 223 16:00 215
05:00 222 17:00 215
06:00 218 18:00 211
07:00 215 19:00 211
08:00 218 20:00 217
09:00 217 21:00 218
10:00 209 22:00 221
11:00 214 23:00 221
12:00 211 24:00 224