Back

Voltage Analysis For 220 KV Panipat Substation For :   19-11-2004

A. Voltage Trend:























B. Voltage Duration Curve:


(Note: The figures shown above are indicative only and are calculated based on data acquired from remote locations
in Northern Region over existing communication links.)

C. Summary Report:

Voltage Greater Than Percentage of Time
245 0
240 0
230 0
227 0
213 12.88
210 36.98
200 100
190 100
Maximum KV 217 KV at 23:43 Hrs.
Minimum KV 202 KV at 10:12 Hrs.
Average KV 209 KV
% of Time Voltage (All values in %)
Between 213-227 KV 12.88
Between 200-245 KV 47.81
<190 KV 00.00
<200 KV 00.00
<210 KV 63.02
<213 KV 87.12
>227 KV 00.00
>230 KV 00.00
>240 KV 00.00
>245 KV 00.00

D. Hourly Values:

Hour KV Hour KV
01:00 212 13:00 208
02:00 211 14:00 208
03:00 211 15:00 209
04:00 210 16:00 207
05:00 208 17:00 207
06:00 206 18:00 206
07:00 206 19:00 205
08:00 211 20:00 209
09:00 208 21:00 214
10:00 205 22:00 213
11:00 207 23:00 214
12:00 204 24:00 215